NFPA 13 · Worked example

Listed CPVC with a submittal bore

A listed CPVC branch has a 1.91 in. internal bore and carries 54 GPM through the entered equivalent length.

Inputs

Pipe and roughness
mm

Use the product submittal or a measured bore.

Hydraulic path
L/min
bar
m
m
m

A negative number represents a downhill run.

m/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP0.37barOUTLET3.63barVELOCITY1.84m/sPIPE BORE48.514mmIN 4 barOUT 3.63 barC 150 · ID 48.514 mmEq. 42.67 mVelocity vs. project limit+2.73 m/s0 m/s4.57 m/s target9.14 m/s
Within velocity screen

Velocity is within the entered limit. Use outlet pressure in the next hydraulic segment.

How to read this example

Enter the actual bore in millimetres in SI mode. The tool applies C = 150 while retaining that product’s internal diameter.

Open the base calculator

Calculated values

Net segment pressure drop
0.37 bar
Predicted outlet pressure
3.63 bar
Mean water velocity
1.84 m/s
Velocity headroom
2.73 m/s
Internal pipe diameter
48.514 mm
Hazen–Williams C
150
Friction gradient
0.00661 bar/m
Total equivalent length
42.67 m
Straight-pipe loss
0.24 bar
Fitting loss
0.04 bar
Friction subtotal
0.28 bar
Signed elevation loss
0.09 bar

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references

Related examples