NFPA 13 · Worked example

Small branch with a velocity limit

An NPS 1¼ Schedule 40 branch carries 90 GPM over 50 ft plus 10 ft of fitting length. The project checks for 15 ft/s.

Inputs

Pipe and roughness
Hydraulic path
GPM
psi
ft
ft
ft

A negative number represents a downhill run.

ft/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP33.19psiOUTLET51.81psiVELOCITY19.31ft/sPIPE BORE1.38inIN 85 psiOUT 51.81 psiC 120 · ID 1.38 inEq. 60 ftVelocity vs. project limit-4.31 ft/s0 ft/s15 ft/s target30 ft/s
Velocity above project limit

Review pipe size, transient effects and the project velocity criterion.

How to read this example

Check the velocity before settling on a diameter. The pressure loss is based on internal bore rather than nominal pipe size.

Open the base calculator

Calculated values

Net segment pressure drop
33.19 psi
Predicted outlet pressure
51.81 psi
Mean water velocity
19.31 ft/s
Velocity headroom
-4.31 ft/s
Internal pipe diameter
1.38 in
Hazen–Williams C
120
Friction gradient
0.55308 psi/ft
Total equivalent length
60 ft
Straight-pipe loss
27.65 psi
Fitting loss
5.53 psi
Friction subtotal
33.19 psi
Signed elevation loss
0 psi

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references

Related examples