GasCompressLab

API 521 · Annexes C and F

API 521 Annex C reference duty

The API 521 Annex C simple example uses 45,360 kg/h, a 468 mm tip and 422 K tip gas.

What to check

Compare estimated stack height at the 45.7 m receptor with the approximate 33 m result from the published nomograph example.

Operating readout

Edit inputs ↓
Receptor flux
6.3kW/m²
Tip Mach
0.199
Min. height
33.31m
Flame length
50m
Receptor radiation exceeds limitThe point-source estimate exceeds the selected ground-level limit.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 8.94 m/sGROUND PLANkW/m²1.58109 m4.7358.6 m9.460 mRECEPTOR LIMIT USED100%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
55.03m/s
Total heat release
630,000kW
Peak ground flux
8.41kW/m²
Flame center downwind shift
21.26m
Flame center above grade
42.29m
Distance from flame center to receptor
48.85m
Service Mach target
0.2
Minimum tip ID for selected Mach
467.39mm
Wind-to-jet velocity ratio
0.162
Downwind extent · 1.58 kW/m²
109.18m
Downwind extent · 4.73 kW/m²
58.55m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.