GasCompressLab

API 521 · Annexes C and F

Calm-wind radiation zones

A calm-wind flare case centers the ground contours at the stack.

What to check

Check the peak at grade and see which thresholds produce nonzero ground zones.

Operating readout

Edit inputs ↓
Receptor flux
3.29kW/m²
Tip Mach
0.257
Min. height
0m
Flame length
55.19m
Within receptor screening levelsModeled receptor radiation and tip Mach meet the selected limits.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 0 m/sGROUND PLANkW/m²1.5889.4 m4.7331.1 m9.460 mRECEPTOR LIMIT USED34.8%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
82.85m/s
Total heat release
775,833.33kW
Peak ground flux
6.51kW/m²
Flame center downwind shift
0m
Flame center above grade
50.59m
Distance from flame center to receptor
71.13m
Service Mach target
0.5
Minimum tip ID for selected Mach
358.32mm
Wind-to-jet velocity ratio
0
Downwind extent · 1.58 kW/m²
89.39m
Downwind extent · 4.73 kW/m²
31.06m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.

Related worked examples