GasCompressLab

API 521 · Annexes C and F

Refinery emergency header flare

A high-rate hydrocarbon relief case is screened at a downwind receptor 70 m from the stack.

What to check

Compare the proposed stack height with the receptor-based minimum and review the emergency Mach limit.

Operating readout

Edit inputs ↓
Receptor flux
2.67kW/m²
Tip Mach
0.197
Min. height
11.09m
Flame length
49.61m
Within receptor screening levelsModeled receptor radiation and tip Mach meet the selected limits.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 9.5 m/sGROUND PLANkW/m²1.5898 m4.7335.2 m9.460 mRECEPTOR LIMIT USED56.4%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
66.91m/s
Total heat release
619,722.22kW
Peak ground flux
5.13kW/m²
Flame center downwind shift
20.21m
Flame center above grade
51.9m
Distance from flame center to receptor
71.92m
Service Mach target
0.5
Minimum tip ID for selected Mach
339.04mm
Wind-to-jet velocity ratio
0.142
Downwind extent · 1.58 kW/m²
97.97m
Downwind extent · 4.73 kW/m²
35.23m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.

Related worked examples