JT · Makogon · MDMT
Hydrogen inverse Joule–Thomson warming
An ambient-temperature hydrogen screen reduces 11,000 kPa(a) to 3,000 kPa(a) with a negative JT coefficient.
The gas warms on expansion in this preset. Confirm the sign and value at the actual inlet state.
Operating readout
Edit inputs ↓- Outlet temp
- 32.8°C
- JT temp change
- 4.8K
- Hydrate margin
- —
- Heater duty
- 0kW
Calculated details
- Hydrate equilibrium estimate
- —
- Gas temperature above MDMT
- 61.8K
- Required upstream temperature lift
- 0K
- Estimated preheated inlet
- 28°C
Operating inputs
Operating inputs
- Upstream pressure P₁
- 11,000kPa(a)
- Downstream pressure P₂
- 3,000kPa(a)
- Upstream temperature
- 28°C
- Gas mass flow
- 580kg/h
- Minimum metal temperature
- -29°C
- Temperature buffer
- 3K
- Gas preset
- Hydrogen H₂
- Gas gravity (air = 1)
- 0.07
- JT coefficient μJT
- -0.06K/bar
- Gas heat capacity Cp
- 14.3kJ/(kg·K)
Calculated details
- Hydrate equilibrium estimate
- —
- Gas temperature above MDMT
- 61.8K
- Required upstream temperature lift
- 0K
- Estimated preheated inlet
- 28°C
Use the hydrate correlation for sweet, water-bearing natural gas in the working screen of G = 0.55–1.00 and 0.5–14 MPa. Treat extrapolation with care. CO₂, nitrogen, and hydrogen need composition-specific hydrate checks. Use a real-gas isenthalpic flash and a metal temperature analysis to assess phase change, water activity, inhibition, and material limits.
Calculation basis
Isenthalpic screening
Use ΔT = −μJT(P₁ − P₂) with a constant user-entered coefficient. A negative coefficient produces warming.
Hydrate and heater screen
Estimate wet natural-gas hydrate temperature from Makogon’s pressure relation with Elgibaly–Elkamel gas-gravity coefficients. Sensible preheater duty is ṁCₚ times the positive deficit to the higher of the hydrate and MDMT screens, including the entered buffer.
Related worked examples
-
Winter city-gate letdown →
Natural gas enters a cold-weather regulator at 16 °C and falls from 7,100 to 1,700 kPa(a).
-
Lean gas metering letdown →
Lean gas enters a modest pressure letdown at 34 °C, allowing a comparison with a water-bearing lean-gas equilibrium estimate.
-
Wet associated gas choke →
A water-bearing associated gas case drops from 9,200 to 3,100 kPa(a) through a production choke.
-
Carbon dioxide pressure letdown →
A CO₂ pressure reduction illustrates a high linear JT coefficient and a low-metal-temperature check.
-
Nitrogen purge regulator →
A nitrogen-only stream passes a purge regulator with a user-entered JT coefficient of 0.28 K/bar.