Winter city-gate letdown

Natural gas enters a cold-weather regulator at 16 °C and falls from 7,100 to 1,700 kPa(a).

What to check

Compare the wet-gas hydrate margin and the steel MDMT margin to identify the governing heater basis.

Operating readout

Edit inputs ↓
Outlet temp
-9.92°C
JT temp change
-25.92K
Hydrate margin
-16.08K
Heater duty
112.96kW
Hydrate screen failedOutlet gas is below the estimated hydrate temperature for wet natural gas.
Choke valve and pressure–temperature pathJT LETDOWN / CHOKEkPa(a)P₁ 7100P₂ 1700ΔT -25.9 KP / T PATHGasHydrateMDMT · °C17.2-297100 kPa(a)1700 kPa(a)PREHEAT REQUIRED20.1 K
The gas and equilibrium curves share a pressure axis. The dashed MDMT line is based on the entered material limit.
Calculated details
Hydrate equilibrium estimate
6.16°C
Gas temperature above MDMT
19.08K
Required upstream temperature lift
20.08K
Estimated preheated inlet
36.08°C

Operating inputs

Letdown duty
kPa(a)
kPa(a)
°C
kg/h
°C
K
Gas properties
Properties are illustrative. Use a representative site value.
K/bar
Edit this value to override the preset. Negative values warm upon expansion.
kJ/(kg·K)

Calculation basis

Isenthalpic screening

Use ΔT = −μJT(P₁ − P₂) with a constant user-entered coefficient. A negative coefficient produces warming.

Hydrate and heater screen

Estimate wet natural-gas hydrate temperature from Makogon’s pressure relation with Elgibaly–Elkamel gas-gravity coefficients. Sensible preheater duty is ṁCₚ times the positive deficit to the higher of the hydrate and MDMT screens, including the entered buffer.