GasCompressLab

API 521 · Restriction orifice

Compressor suction scrubber depressuring

A gas scrubber is screened to nominal 100 psig with the isothermal inventory option.

What to check

The isothermal option holds bulk gas temperature fixed. Use the adiabatic setting to bracket cooling sensitivity.

Operating readout

Edit inputs ↓
Time to target
12.27min
Peak flow
4,113.28kg/h
Min. gas temp
35°C
15-min RO ID
17.184mm
Within 15-minute benchmarkThe selected pressure target is reached on the entered tank and orifice model.
Vessel blowdown pressure and mass-flow decayVESSEL / RESTRICTION / HEADERmmGas inventoryRO 19DEPRESSURINGP · kPa(a)Flow · kg/h2700791411000 min15.6 min15-MINUTE SCREEN12.3 min
Pressure and mass flow use independent scales. The vertical gate marks 15 minutes, and the plotted curves end at the selected pressure target.
Calculated details
Selected absolute target
790.8kPa(a)
Initial vapor inventory
684.98kg
Choked/subsonic transition pressure
371.34kPa(a)
Transition time if crossed
—
Starting regime
Choked
Target regime
Choked
Minimum gas temperature above MDMT
64K

Operating inputs

Vessel and target
m³
bar(a)
°C
kPa(a)
°C
Restriction and gas
mm
kg/kmol

Calculation basis

Inventory and discharge

Use a uniform vapor inventory with fixed Z and k. Pressure follows mass to the power k for adiabatic operation, or mass directly for isothermal operation. Compute instantaneous gas flux with the choked expression below the critical backpressure ratio and the subsonic nozzle expression above it.

Integrate time

Integrate dM/ṁ down to the selected pressure with a transformed pressure coordinate. Solve the 15-minute orifice diameter using the inverse-area time scaling for this model.

Related worked examples