High-rise two-span mullion

A continuous mullion passes over a floor anchor with equal spans and similar loaded bays.

L/175 · L/240 · 19 mm cap

Inputs

Span and loading
m
m
kPa
Aluminum section
cm⁴
cm³
GPa
MPa

0 uses the illustrative alloy allowance.

Screening result

Mullion deflection or bending stress exceeds the selected limit.

Fail
Deflection
21.77mm
Service limit
19mm
Bend stress
119MPa
Bending use
72.1%
Curtain-wall tributary loading and beam responseCurtain-wall mullion. Deflection 21.77 mm. Service limit 19 mm. Bend stress 119 MPa. Bending use 72.1 %.Wind load onto mullionTrapezoidal · span 4.45 mPeak 3.85 kN/mOut-of-plane responseTwo equal continuous spansMδMomentDeflectionGoverning mullion demand0%100% limit200%+

Calculation details

Peak tributary line load
3.848 kN/m
Maximum absolute bending moment
9.042 kN·m
Uncapped L/175
25.429 mm
L/175 with long-span cap
19 mm
L/240 reference
18.542 mm
Elastic modulus
69 GPa
Selected bending allowance
165 MPa
Deflection utilization
114.6 %

Formula trace in SI

  1. Tributary wind

    w(x) = q min(B, 2x, 2(L − x))

    Trapezoidal load, peak 3.848 kN/m.

  2. Beam response

    EI y″ = M(x); σ = |M|max / Sx

    Zero rotation at the common support. |M|max = 9.042 kN·m, δmax = 21.773 mm.

  3. Service criterion

    δallow = L/175, capped at 19 mm if L > 4.1 m

    Selected 19 mm, deflection use 114.59 %.

  4. Bending criterion

    Utilization = σ / σallow

    118.974 MPa / 165 MPa = 72.11 %.