Narrow corner mullion strip

A narrow tributary width and high suction apply to a pressure-zone corner.

L/175 · L/240 · 19 mm cap

Inputs

Span and loading
m
m
kPa
Aluminum section
cm⁴
cm³
GPa
MPa

0 uses the illustrative alloy allowance.

Screening result

Mullion deflection or bending stress exceeds the selected limit.

Fail
Deflection
24.47mm
Service limit
21.26mm
Bend stress
99.2MPa
Bending use
104.5%
Curtain-wall tributary loading and beam responseCurtain-wall mullion. Deflection 24.47 mm. Service limit 21.26 mm. Bend stress 99.2 MPa. Bending use 104.5 %.Wind load onto mullionTrapezoidal · span 3.72 mPeak 2.44 kN/mOut-of-plane responseSimply supported spanMδMomentDeflectionGoverning mullion demand0%100% limit200%+

Calculation details

Peak tributary line load
2.442 kN/m
Maximum absolute bending moment
4.168 kN·m
Uncapped L/175
21.257 mm
L/175 with long-span cap
21.257 mm
L/240 reference
15.5 mm
Elastic modulus
69 GPa
Selected bending allowance
95 MPa
Deflection utilization
115.1 %

Formula trace in SI

  1. Tributary wind

    w(x) = q min(B, 2x, 2(L − x))

    Trapezoidal load, peak 2.442 kN/m.

  2. Beam response

    EI y″ = M(x); σ = |M|max / Sx

    Zero displacement at both pins. |M|max = 4.168 kN·m, δmax = 24.467 mm.

  3. Service criterion

    δallow = L/175, capped at 19 mm if L > 4.1 m

    Selected 21.257 mm, deflection use 115.1 %.

  4. Bending criterion

    Utilization = σ / σallow

    99.249 MPa / 95 MPa = 104.47 %.