GlassFacadeLab · L/175 · L/240 · 19 mm cap
Hospital L/240 service check
Worked example · SI
Fail · Mullion deflection or bending stress exceeds the selected limit.
Inputs
- Span L per bay
- 3.4 m
- Tributary spacing B
- 1.35 m
- Wind pressure magnitude
- 1.75 kPa
- Support condition
- Simply supported
- Service limit
- Also check L/240
- Second moment Iₓ
- 365 cm⁴
- Section modulus Sₓ
- 44 cm³
- Extrusion alloy
- 6063-T6
- Elastic modulus E
- 69 GPa
- Bending allowance override
- 0 MPa
Results
- Deflection
- 15.31 mm
- Service limit
- 14.17 mm
- Bend stress
- 73.5 MPa
- Bending use
- 66.8 %
- Peak tributary line load
- 2.363 kN/m
- Maximum absolute bending moment
- 3.234 kN·m
- Uncapped L/175
- 19.429 mm
- L/175 with long-span cap
- 19.429 mm
- L/240 reference
- 14.167 mm
- Elastic modulus
- 69 GPa
- Selected bending allowance
- 110 MPa
- Deflection utilization
- 108.1 %
Formula trace in SI
Tributary wind
w(x) = q min(B, 2x, 2(L − x))
Trapezoidal load, peak 2.363 kN/m.
Beam response
EI y″ = M(x); σ = |M|max / Sx
Zero displacement at both pins. |M|max = 3.234 kN·m, δmax = 15.309 mm.
Service criterion
δallow = L/175, capped at 19 mm if L > 4.1 m
Selected 14.167 mm, deflection use 108.07 %. L/240 also applies.
Bending criterion
Utilization = σ / σallow
73.509 MPa / 110 MPa = 66.83 %.