Hospital L/240 service check

A rigid interior finish next to the curtain wall motivates a stricter movement allowance.

L/175 · L/240 · 19 mm cap

Inputs

Span and loading
m
m
kPa
Aluminum section
cm⁴
cm³
GPa
MPa

0 uses the illustrative alloy allowance.

Screening result

Mullion deflection or bending stress exceeds the selected limit.

Fail
Deflection
15.31mm
Service limit
14.17mm
Bend stress
73.5MPa
Bending use
66.8%
Curtain-wall tributary loading and beam responseCurtain-wall mullion. Deflection 15.31 mm. Service limit 14.17 mm. Bend stress 73.5 MPa. Bending use 66.8 %.Wind load onto mullionTrapezoidal · span 3.4 mPeak 2.36 kN/mOut-of-plane responseSimply supported spanMδMomentDeflectionGoverning mullion demand0%100% limit200%+

Calculation details

Peak tributary line load
2.363 kN/m
Maximum absolute bending moment
3.234 kN·m
Uncapped L/175
19.429 mm
L/175 with long-span cap
19.429 mm
L/240 reference
14.167 mm
Elastic modulus
69 GPa
Selected bending allowance
110 MPa
Deflection utilization
108.1 %

Formula trace in SI

  1. Tributary wind

    w(x) = q min(B, 2x, 2(L − x))

    Trapezoidal load, peak 2.363 kN/m.

  2. Beam response

    EI y″ = M(x); σ = |M|max / Sx

    Zero displacement at both pins. |M|max = 3.234 kN·m, δmax = 15.309 mm.

  3. Service criterion

    δallow = L/175, capped at 19 mm if L > 4.1 m

    Selected 14.167 mm, deflection use 108.07 %. L/240 also applies.

  4. Bending criterion

    Utilization = σ / σallow

    73.509 MPa / 110 MPa = 66.83 %.