GlassFacadeLab · L/175 · L/240 · 19 mm cap
Narrow corner mullion strip
Worked example · SI
Fail · Mullion deflection or bending stress exceeds the selected limit.
Inputs
- Span L per bay
- 3.72 m
- Tributary spacing B
- 0.74 m
- Wind pressure magnitude
- 3.3 kPa
- Support condition
- Simply supported
- Service limit
- L/175 with long-span cap
- Second moment Iₓ
- 355 cm⁴
- Section modulus Sₓ
- 42 cm³
- Extrusion alloy
- 6063-T6
- Elastic modulus E
- 69 GPa
- Bending allowance override
- 95 MPa
Results
- Deflection
- 24.47 mm
- Service limit
- 21.26 mm
- Bend stress
- 99.2 MPa
- Bending use
- 104.5 %
- Peak tributary line load
- 2.442 kN/m
- Maximum absolute bending moment
- 4.168 kN·m
- Uncapped L/175
- 21.257 mm
- L/175 with long-span cap
- 21.257 mm
- L/240 reference
- 15.5 mm
- Elastic modulus
- 69 GPa
- Selected bending allowance
- 95 MPa
- Deflection utilization
- 115.1 %
Formula trace in SI
Tributary wind
w(x) = q min(B, 2x, 2(L − x))
Trapezoidal load, peak 2.442 kN/m.
Beam response
EI y″ = M(x); σ = |M|max / Sx
Zero displacement at both pins. |M|max = 4.168 kN·m, δmax = 24.467 mm.
Service criterion
δallow = L/175, capped at 19 mm if L > 4.1 m
Selected 21.257 mm, deflection use 115.1 %.
Bending criterion
Utilization = σ / σallow
99.249 MPa / 95 MPa = 104.47 %.