GlassFacadeLab · Solar absorption · Edge restraint
Solar thermal-stress and edge breakage calculator
Calculator scenario · SI
Fail · Modeled tensile stress exceeds the selected edge allowance.
Inputs
- Solar absorptance
- 0.46
- Peak solar irradiance
- 780 W/m²
- Indoor reference temperature
- 22 °C
- Shaded edge temperature
- 12 °C
- Frame shadow band
- 47 mm
- Effective heat transfer
- 15 W/(m²·K)
- Edge finish
- Clean-cut
- Glass treatment
- Annealed
- Clean-cut annealed allowance
- 18 MPa
Results
- Center–edge ΔT
- 33.9 K
- Edge stress
- 18.07 MPa
- Edge allowance
- 18 MPa
- Safety factor
- 0.996
- Sunlit center temperature
- 45.92 °C
- Shaded edge temperature
- 12 °C
- Absorbed solar flux
- 358.8 W/m²
- Frame restraint assumption
- 0.846
- Edge stress utilization
- 100.4 %
Formula trace in SI
Absorbed heat
qsolar = α I; Tcenter = Tindoor + qsolar/heff
Absorbed 358.8 W/m², center 45.92 °C.
Edge tension
σth = E αglass max(ΔT, 0) Kframe
ΔT 33.92 K, Kframe 0.846, stress 18.07 MPa.
Edge allowance
σallow = σref × edge factor × treatment factor
Factors 1 × 1, allowance 18 MPa.