Fin-fan air cooler efficiency & fan power
Compare fin geometry and surface efficiency, then calculate air flow and shaft power for a specified heat load.
Finned tube and air path
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
- Fin efficiency
- 85.178%
- Surface eff.
- 85.959%
- Area ratio
- 16.597
- Shaft power
- 3.4537kW
- Within the displayed screening checks.
Inputs
Calculated results
- Fin efficiency
- 85.178 %
- Overall surface efficiency
- 85.959 %
- Total / bare tube area
- 16.597
- Fan shaft power
- 3.4537 kW
- Required air mass flow
- 13.917 kg/s
- Required air volume flow
- 11.997 m³/s
- Air temperature rise
- 15 K
- Complete fins
- 211,680
- Total airside area
- 889.98 m²
- Reference bare tube area
- 53.623 m²
- Efficiency-weighted area
- 765.02 m²
- Shaft power budget
- 4 kW
- Shaft power headroom
- 13.658 %
Calculation basis
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.