HeatExchangerLab

Steel fin efficiency in hot service

A hot industrial service uses steel fins with lower conductivity than aluminum.

Finned tube and air path

ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan

Edit inputs ↓
Fin efficiency
45.792%
Surface eff.
48.042%
Area ratio
19.655
Shaft power
5.2714kW
Finned tube and air pathFIN SECTIONAIR PATH →Annular discFan at design flow0Shaft budget150% load
The plate or disc shape, tube radius, and fin density drive the cutaway. The bar compares required shaft power to the entered budget.
  • Required fan shaft power exceeds the entered budget.

Inputs

mm
mm
mm
fins/cm
m
W/(m·K)
W/(m²·K)
kW
K
kJ/(kg·K)
kg/m³
kPa
%
kW

Calculated results

Fin efficiency
45.792 %
Overall surface efficiency
48.042 %
Total / bare tube area
19.655
Fan shaft power
5.2714 kW
Required air mass flow
13.047 kg/s
Required air volume flow
12.425 m³/s
Air temperature rise
24 K
Complete fins
137,760
Total airside area
1,053.9 m²
Reference bare tube area
53.623 m²
Efficiency-weighted area
506.33 m²
Shaft power budget
4.1 kW
Shaft power headroom
-28.571 %

Worked solution

Preset calculation · Metric SI

  1. Count 137,760 complete fins across the tube bundle. The exposed and finned surfaces total 1,053.9 m².
  2. Apply 45.792 % fin efficiency to the fin area. The area-weighted result is 48.042 % surface efficiency.
  3. The air heat balance requires 12.425 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 5.2714 kW shaft power.

Compare the larger geometric area with the reduced effective area. Enter the alternative conductivity to see the efficiency impact.

Calculation basis

Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.

Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.

Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.

Methodology and references