Annular aluminum fin process cooler
An air-cooled exchanger uses aluminum disc fins around ¾-inch process tubes.
Finned tube and air path
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
- Fin efficiency
- 84.701%
- Surface eff.
- 85.322%
- Area ratio
- 21.089
- Shaft power
- 4.5524kW
- Within the displayed screening checks.
Inputs
Calculated results
- Fin efficiency
- 84.701 %
- Overall surface efficiency
- 85.322 %
- Total / bare tube area
- 21.089
- Fan shaft power
- 4.5524 kW
- Required air mass flow
- 15.842 kg/s
- Required air volume flow
- 13.657 m³/s
- Air temperature rise
- 16 K
- Complete fins
- 333,450
- Total airside area
- 1,079.1 m²
- Reference bare tube area
- 51.169 m²
- Efficiency-weighted area
- 920.71 m²
- Shaft power budget
- 5.6 kW
- Shaft power headroom
- 18.707 %
Worked solution
Preset calculation · Metric SI
- Count 333,450 complete fins across the tube bundle. The exposed and finned surfaces total 1,079.1 m².
- Apply 84.701 % fin efficiency to the fin area. The area-weighted result is 85.322 % surface efficiency.
- The air heat balance requires 13.657 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 4.5524 kW shaft power.
Compare fin efficiency, weighted surface efficiency, and the estimated shaft-power reserve.
Calculation basis
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.
Methodology and references