HeatExchangerLab

Air cooler constrained by fan shaft power

A high-duty service must keep a small air temperature rise while the existing fan has a fixed shaft-power allowance.

Finned tube and air path

ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan

Edit inputs ↓
Fin efficiency
86.472%
Surface eff.
87.056%
Area ratio
19.153
Shaft power
34.154kW
Finned tube and air pathFIN SECTIONAIR PATH →Annular discFan at design flow0Shaft budget150% load
The plate or disc shape, tube radius, and fin density drive the cutaway. The bar compares required shaft power to the entered budget.
  • Required fan shaft power exceeds the entered budget.

Inputs

mm
mm
mm
fins/cm
m
W/(m·K)
W/(m²·K)
kW
K
kJ/(kg·K)
kg/m³
kPa
%
kW

Calculated results

Fin efficiency
86.472 %
Overall surface efficiency
87.056 %
Total / bare tube area
19.153
Fan shaft power
34.154 kW
Required air mass flow
55.576 kg/s
Required air volume flow
55.025 m³/s
Air temperature rise
11 K
Complete fins
430,140
Total airside area
1,962.4 m²
Reference bare tube area
102.46 m²
Efficiency-weighted area
1,708.4 m²
Shaft power budget
18 kW
Shaft power headroom
-89.743 %

Worked solution

Preset calculation · Metric SI

  1. Count 430,140 complete fins across the tube bundle. The exposed and finned surfaces total 1,962.4 m².
  2. Apply 86.472 % fin efficiency to the fin area. The area-weighted result is 87.056 % surface efficiency.
  3. The air heat balance requires 55.025 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 34.154 kW shaft power.

Check the budget overrun. Air temperature rise, pressure drop and fan efficiency determine the shaft-power estimate.

Calculation basis

Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.

Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.

Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.

Methodology and references