Rectangular fin air-cooler panel

A prefabricated cooler uses square outer fin plates punched for a circular tube.

Finned tube and air path

ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan

Edit inputs ↓
Fin efficiency
92.404%
Surface eff.
92.887%
Area ratio
13.766
Shaft power
4.5064kW
Finned tube and air pathFIN SECTIONAIR PATH →Rectangular plateFan at design flow0Shaft budget150% load
The plate or disc shape, tube radius, and fin density drive the cutaway. The bar compares required shaft power to the entered budget.
  • Within the displayed screening checks.

Inputs

mm
mm
mm
fins/cm
m
W/(m·K)
W/(m²·K)
kW
K
kJ/(kg·K)
kg/m³
kPa
%
kW

Calculated results

Fin efficiency
92.404 %
Overall surface efficiency
92.887 %
Total / bare tube area
13.766
Fan shaft power
4.5064 kW
Required air mass flow
14.082 kg/s
Required air volume flow
12.14 m³/s
Air temperature rise
12 K
Complete fins
120,250
Total airside area
457.63 m²
Reference bare tube area
33.244 m²
Efficiency-weighted area
425.08 m²
Shaft power budget
4.8 kW
Shaft power headroom
6.1158 %

Worked solution

Preset calculation · Metric SI

  1. Count 120,250 complete fins across the tube bundle. The exposed and finned surfaces total 457.63 m².
  2. Apply 92.404 % fin efficiency to the fin area. The area-weighted result is 92.887 % surface efficiency.
  3. The air heat balance requires 12.14 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 4.5064 kW shaft power.

Compare area ratio with an annular fin at the same half-width. Geometry changes area and fin efficiency while the air energy balance stays fixed.

Calculation basis

Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.

Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.

Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.