HeatExchangerLab

Fin-fan air cooler efficiency & fan power

Compare fin geometry and surface efficiency, then calculate air flow and shaft power for a specified heat load.

Finned tube and air path

ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan

Edit inputs ↓
Fin efficiency
85.178%
Surface eff.
85.959%
Area ratio
16.597
Shaft power
3.4537kW
Finned tube and air pathFIN SECTIONAIR PATH →Annular discFan at design flow0Shaft budget150% load
The plate or disc shape, tube radius, and fin density drive the cutaway. The bar compares required shaft power to the entered budget.
  • Within the displayed screening checks.

Inputs

mm
mm
mm
fins/cm
m
W/(m·K)
W/(m²·K)
kW
K
kJ/(kg·K)
kg/m³
kPa
%
kW

Calculated results

Fin efficiency
85.178 %
Overall surface efficiency
85.959 %
Total / bare tube area
16.597
Fan shaft power
3.4537 kW
Required air mass flow
13.917 kg/s
Required air volume flow
11.997 m³/s
Air temperature rise
15 K
Complete fins
211,680
Total airside area
889.98 m²
Reference bare tube area
53.623 m²
Efficiency-weighted area
765.02 m²
Shaft power budget
4 kW
Shaft power headroom
13.658 %

Calculation basis

Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.

Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.

Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.

Methodology and references