Air cooler constrained by fan shaft power
A high-duty service must keep a small air temperature rise while the existing fan has a fixed shaft-power allowance.
Finned tube and air path
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
- Fin efficiency
- 86.472%
- Surface eff.
- 87.056%
- Area ratio
- 19.153
- Shaft power
- 34.154kW
- Required fan shaft power exceeds the entered budget.
Inputs
Calculated results
- Fin efficiency
- 86.472 %
- Overall surface efficiency
- 87.056 %
- Total / bare tube area
- 19.153
- Fan shaft power
- 34.154 kW
- Required air mass flow
- 55.576 kg/s
- Required air volume flow
- 55.025 m³/s
- Air temperature rise
- 11 K
- Complete fins
- 430,140
- Total airside area
- 1,962.4 m²
- Reference bare tube area
- 102.46 m²
- Efficiency-weighted area
- 1,708.4 m²
- Shaft power budget
- 18 kW
- Shaft power headroom
- -89.743 %
Worked solution
Preset calculation · Metric SI
- Count 430,140 complete fins across the tube bundle. The exposed and finned surfaces total 1,962.4 m².
- Apply 86.472 % fin efficiency to the fin area. The area-weighted result is 87.056 % surface efficiency.
- The air heat balance requires 55.025 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 34.154 kW shaft power.
Check the budget overrun. Air temperature rise, pressure drop and fan efficiency determine the shaft-power estimate.
Calculation basis
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.
Methodology and references