Rectangular fin air-cooler panel
A prefabricated cooler uses square outer fin plates punched for a circular tube.
Finned tube and air path
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
- Fin efficiency
- 92.404%
- Surface eff.
- 92.887%
- Area ratio
- 13.766
- Shaft power
- 4.5064kW
- Within the displayed screening checks.
Inputs
Calculated results
- Fin efficiency
- 92.404 %
- Overall surface efficiency
- 92.887 %
- Total / bare tube area
- 13.766
- Fan shaft power
- 4.5064 kW
- Required air mass flow
- 14.082 kg/s
- Required air volume flow
- 12.14 m³/s
- Air temperature rise
- 12 K
- Complete fins
- 120,250
- Total airside area
- 457.63 m²
- Reference bare tube area
- 33.244 m²
- Efficiency-weighted area
- 425.08 m²
- Shaft power budget
- 4.8 kW
- Shaft power headroom
- 6.1158 %
Worked solution
Preset calculation · Metric SI
- Count 120,250 complete fins across the tube bundle. The exposed and finned surfaces total 457.63 m².
- Apply 92.404 % fin efficiency to the fin area. The area-weighted result is 92.887 % surface efficiency.
- The air heat balance requires 12.14 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 4.5064 kW shaft power.
Compare area ratio with an annular fin at the same half-width. Geometry changes area and fin efficiency while the air energy balance stays fixed.
Calculation basis
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.