Steel fin efficiency in hot service
A hot industrial service uses steel fins with lower conductivity than aluminum.
Finned tube and air path
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
- Fin efficiency
- 45.792%
- Surface eff.
- 48.042%
- Area ratio
- 19.655
- Shaft power
- 5.2714kW
- Required fan shaft power exceeds the entered budget.
Inputs
Calculated results
- Fin efficiency
- 45.792 %
- Overall surface efficiency
- 48.042 %
- Total / bare tube area
- 19.655
- Fan shaft power
- 5.2714 kW
- Required air mass flow
- 13.047 kg/s
- Required air volume flow
- 12.425 m³/s
- Air temperature rise
- 24 K
- Complete fins
- 137,760
- Total airside area
- 1,053.9 m²
- Reference bare tube area
- 53.623 m²
- Efficiency-weighted area
- 506.33 m²
- Shaft power budget
- 4.1 kW
- Shaft power headroom
- -28.571 %
Worked solution
Preset calculation · Metric SI
- Count 137,760 complete fins across the tube bundle. The exposed and finned surfaces total 1,053.9 m².
- Apply 45.792 % fin efficiency to the fin area. The area-weighted result is 48.042 % surface efficiency.
- The air heat balance requires 12.425 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 5.2714 kW shaft power.
Compare the larger geometric area with the reduced effective area. Enter the alternative conductivity to see the efficiency impact.
Calculation basis
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.
Methodology and references