HeatExchangerLab

Counterflow with equal terminal approaches

A process-water recovery exchanger cools the hot stream by 40 K while warming the cold stream by 40 K.

Terminal temperature profile

Q = U × A × Fₜ × ΔTₗₘ

Edit inputs ↓
Area needed
20m²
LMTD
55K
Fₜ factor
1
Rated duty
792kW
Terminal temperature profile120 °C80 °C65 °C25 °CHOT STREAM →← COLD STREAMEnd AEnd BFₜ 00.75 screenFₜ 1
The lines join terminal temperatures along the hot-stream direction. Shell cases use a counterflow reference for the temperature plot.
  • Within the displayed screening checks.

Inputs

°C
°C
°C
°C
kW
W/(m²·K)
m²

Calculated results

Required surface
20 m²
Log mean ΔT
55 K
Correction factor Fₜ
1
Available duty
792 kW
Target duty
660 kW
Corrected mean ΔT
55 K
Terminal difference A
55 K
Terminal difference B
55 K
Cold temperature ratio P
0.42105
Stream temperature ratio R
1
Duty reserve vs. target
20 %

Worked solution

Preset calculation · Metric SI

  1. Pair the terminal temperatures to obtain 55 K and 55 K. Their log mean is 55 K.
  2. Use P = 0.42105 and R = 1 for the shell correction where applicable. Fₜ = 1.
  3. Divide 660 kW by 600 W/(m²·K) times the corrected drive of 55 K to obtain 20 m².

Both terminal approaches are 55 K. Check that the mean is exactly 55 K and that 20 m² meets the target.

Calculation basis

Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.

The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.

For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.

Methodology and references