Low Fₜ on a process-feed exchanger
A proposed one-shell exchanger drives both streams through large temperature changes, close to its correction-factor limit.
Terminal temperature profile
Q = U × A × Fₜ × ΔTₗₘ
- Area needed
- 58.648m²
- LMTD
- 58.877K
- Fₜ factor
- 0.74662
- Rated duty
- 1,688kW
- Fₜ is below 0.75. Check the temperature cross and compare a different shell arrangement.
- Cold outlet meets or exceeds hot outlet. Check the terminal approaches and the selected flow arrangement.
Inputs
Calculated results
- Required surface
- 58.648 m²
- Log mean ΔT
- 58.877 K
- Correction factor Fₜ
- 0.74662
- Available duty
- 1,688 kW
- Target duty
- 1,650 kW
- Corrected mean ΔT
- 43.959 K
- Terminal difference A
- 49 K
- Terminal difference B
- 70 K
- Cold temperature ratio P
- 0.608
- Stream temperature ratio R
- 0.72368
- Duty reserve vs. target
- 2.3047 %
Worked solution
Preset calculation · Metric SI
- Pair the terminal temperatures to obtain 49 K and 70 K. Their log mean is 58.877 K.
- Use P = 0.608 and R = 0.72368 for the shell correction where applicable. Fₜ = 0.74662.
- Divide 1,650 kW by 640 W/(m²·K) times the corrected drive of 43.959 K to obtain 58.648 m².
Use the 0.75 marker to screen the temperature program. Compare the required area after switching to two shell passes.
Calculation basis
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.