Glycol heat recovery with a small pinch
A counterflow exchanger recovers heat into a glycol loop. Both ends approach the minimum practical temperature gap.
Terminal temperature profile
Q = U × A × Fₜ × ΔTₗₘ
- Area needed
- 82.987m²
- LMTD
- 9.6924K
- Fₜ factor
- 1
- Rated duty
- 254.14kW
- Cold outlet meets or exceeds hot outlet. Check the terminal approaches and the selected flow arrangement.
- Available surface falls short of the target duty.
Inputs
Calculated results
- Required surface
- 82.987 m²
- Log mean ΔT
- 9.6924 K
- Correction factor Fₜ
- 1
- Available duty
- 254.14 kW
- Target duty
- 370 kW
- Corrected mean ΔT
- 9.6924 K
- Terminal difference A
- 13 K
- Terminal difference B
- 7 K
- Cold temperature ratio P
- 0.77966
- Stream temperature ratio R
- 1.1304
- Duty reserve vs. target
- -31.315 %
Worked solution
Preset calculation · Metric SI
- Pair the terminal temperatures to obtain 13 K and 7 K. Their log mean is 9.6924 K.
- Use P = 0.77966 and R = 1.1304 for the shell correction where applicable. Fₜ = 1.
- Divide 370 kW by 460 W/(m²·K) times the corrected drive of 9.6924 K to obtain 82.987 m².
Check the surface required with the 7 K cold-end gap. Raising the hot outlet by a few kelvin shows how the pinch controls area.
Calculation basis
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.