HeatExchangerLab

Glycol heat recovery with a small pinch

A counterflow exchanger recovers heat into a glycol loop. Both ends approach the minimum practical temperature gap.

Terminal temperature profile

Q = U × A × Fₜ × ΔTₗₘ

Edit inputs ↓
Area needed
82.987m²
LMTD
9.6924K
Fₜ factor
1
Rated duty
254.14kW
Terminal temperature profile94 °C42 °C81 °C35 °CHOT STREAM →← COLD STREAMEnd AEnd BFₜ 00.75 screenFₜ 1
The lines join terminal temperatures along the hot-stream direction. Shell cases use a counterflow reference for the temperature plot.
  • Cold outlet meets or exceeds hot outlet. Check the terminal approaches and the selected flow arrangement.
  • Available surface falls short of the target duty.

Inputs

°C
°C
°C
°C
kW
W/(m²·K)
m²

Calculated results

Required surface
82.987 m²
Log mean ΔT
9.6924 K
Correction factor Fₜ
1
Available duty
254.14 kW
Target duty
370 kW
Corrected mean ΔT
9.6924 K
Terminal difference A
13 K
Terminal difference B
7 K
Cold temperature ratio P
0.77966
Stream temperature ratio R
1.1304
Duty reserve vs. target
-31.315 %

Worked solution

Preset calculation · Metric SI

  1. Pair the terminal temperatures to obtain 13 K and 7 K. Their log mean is 9.6924 K.
  2. Use P = 0.77966 and R = 1.1304 for the shell correction where applicable. Fₜ = 1.
  3. Divide 370 kW by 460 W/(m²·K) times the corrected drive of 9.6924 K to obtain 82.987 m².

Check the surface required with the 7 K cold-end gap. Raising the hot outlet by a few kelvin shows how the pinch controls area.

Calculation basis

Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.

The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.

For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.