2–4 feed–effluent heat recovery
A feed–effluent train uses two ideal shell passes. The warmed feed leaves above the effluent outlet temperature.
Terminal temperature profile
Q = U × A × Fₜ × ΔTₗₘ
- Area needed
- 79.574m²
- LMTD
- 64.343K
- Fₜ factor
- 0.94811
- Rated duty
- 3,298.8kW
- Cold outlet meets or exceeds hot outlet. Check the terminal approaches and the selected flow arrangement.
Inputs
Calculated results
- Required surface
- 79.574 m²
- Log mean ΔT
- 64.343 K
- Correction factor Fₜ
- 0.94811
- Available duty
- 3,298.8 kW
- Target duty
- 2,500 kW
- Corrected mean ΔT
- 61.005 K
- Terminal difference A
- 59 K
- Terminal difference B
- 70 K
- Cold temperature ratio P
- 0.56296
- Stream temperature ratio R
- 0.85526
- Duty reserve vs. target
- 31.953 %
Worked solution
Preset calculation · Metric SI
- Pair the terminal temperatures to obtain 59 K and 70 K. Their log mean is 64.343 K.
- Use P = 0.56296 and R = 0.85526 for the shell correction where applicable. Fₜ = 0.94811.
- Divide 2,500 kW by 515 W/(m²·K) times the corrected drive of 61.005 K to obtain 79.574 m².
Check the outlet cross and the positive terminal gaps. Compare the 2–4 correction factor to the 1–2 case at the same temperatures.
Calculation basis
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.