Low-conductivity polymer wall panel
An industrial recovery panel uses a polymer barrier between two liquids.
Thermal resistance stack
U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k
- Clean U
- 135.48W/(m²·K)
- Service U
- 130.7W/(m²·K)
- Cleanliness
- 96.471%
- Largest term
- Metal wall
- Within the displayed screening checks.
Inputs
Calculated results
- Clean overall U
- 135.48 W/(m²·K)
- Fouled service U
- 130.7 W/(m²·K)
- Cleanliness
- 96.471 %
- Controlling resistance
- Metal wall
- Total fouled resistance
- 0.0076513 m²·K/W
- Inside film resistance
- 0.00057143 m²·K/W
- Inside fouling resistance
- 0.00015 m²·K/W
- Wall resistance
- 0.0057895 m²·K/W
- Outside fouling resistance
- 0.00012 m²·K/W
- Outside film resistance
- 0.0010204 m²·K/W
- Fouling loss in U
- 3.5288 %
Worked solution
Preset calculation · Metric SI
- Put both films, both fouling terms, and the wall on one surface basis. The wall contributes 0.0057895 m²·K/W.
- Sum the resistances to get 0.0076513 m²·K/W. Its reciprocal gives service U of 130.7 W/(m²·K).
- Omit the fouling terms to get clean U of 135.48 W/(m²·K), then divide service U by clean U for 96.471 % cleanliness.
The wall dominates here. Changing only a film coefficient shows how little the service U improves.
Calculation basis
For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.
For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.
Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.