Viscous oil film in a carbon-steel tube
A viscous heat-transfer oil runs in the tubes while water flows outside.
Thermal resistance stack
U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k
- Clean U
- 126.24W/(m²·K)
- Service U
- 120.41W/(m²·K)
- Cleanliness
- 95.381%
- Largest term
- Inside film
- Within the displayed screening checks.
Inputs
Calculated results
- Clean overall U
- 126.24 W/(m²·K)
- Fouled service U
- 120.41 W/(m²·K)
- Cleanliness
- 95.381 %
- Controlling resistance
- Inside film
- Total fouled resistance
- 0.0083052 m²·K/W
- Inside film resistance
- 0.0074882 m²·K/W
- Inside fouling resistance
- 0.00026358 m²·K/W
- Wall resistance
- 4.88e-5 m²·K/W
- Outside fouling resistance
- 0.00012 m²·K/W
- Outside film resistance
- 0.00038462 m²·K/W
- Fouling loss in U
- 4.6186 %
Worked solution
Preset calculation · Metric SI
- Put both films, both fouling terms, and the wall on one surface basis. The wall contributes 4.88e-5 m²·K/W.
- Sum the resistances to get 0.0083052 m²·K/W. Its reciprocal gives service U of 120.41 W/(m²·K).
- Omit the fouling terms to get clean U of 126.24 W/(m²·K), then divide service U by clean U for 95.381 % cleanliness.
Compare the inside film with both fouling terms. Cleaner surfaces provide limited improvement when the oil film controls.
Calculation basis
For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.
For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.
Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.