Office exit corridor on 24 V
Check a corridor with a common emergency-output retention factor and compute the battery Ah from real AC load.
Inputs
View results ↑- Initial avg.
- 1.35fc
- 90-min avg.
- 0.95fc
- Worst max:min
- 22.5:1
- Battery bank
- 12.43Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Within screen- Initial mean1.35 / ≥ 1 fc within screen
- Initial minimum0.16 / ≥ 0.1 fc within screen
- 90-minute mean0.945 / ≥ 0.6 fc within screen
- 90-minute minimum0.112 / ≥ 0.06 fc within screen
- Initial max / min22.5 / ≤ 40 :1 within screen
- 90-minute max / min22.5 / ≤ 40 :1 within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 910ft² |
|---|---|
| Total initial fixture output | 13,300lm |
| Emitted flux per floor area | 14.62lm/ft² |
| Initial minimum | 0.16fc |
| Initial maximum | 3.6fc |
| Initial max / min | 22.5:1 |
| 90-minute minimum | 0.11fc |
| 90-minute maximum | 2.52fc |
| 90-minute max / min | 22.5:1 |
| Inverter real load | 140W |
| Inverter apparent load | 180VA |
| Assumed fixture power factor | 0.778 |
| Estimated DC current | 6.63A |
| DC energy before derating | 238.64Wh |
Worked calculation
US customary results for the original preset.
- The initial average and minimum are 1.35 fc and 0.16 fc. The corresponding 90-minute values are 0.95 fc and 0.11 fc.
- The worst maximum-to-minimum ratio is 22.5:1 against the 40:1 limit.
- The inverter supplies 180 VA and 140 W. For 90 minutes, the estimated derated bank is 12.43 Ah.
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗Office exit corridor on 24 V
Inputs
| Egress path length | 130ft |
|---|---|
| Path clear width | 7ft |
| Initial average | 1.35fc |
| Initial minimum | 0.16fc |
| Initial maximum | 3.6fc |
| 90-minute readings | Apply output retention factor |
| End-of-discharge retention | 0.7 |
| Emergency fixtures | 10 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 14W |
| Apparent input per fixture | 18VA |
| Battery system voltage | 24 V DC |
| Inverter efficiency | 0.88 |
| Battery aging / temperature factor | 1.25× |
Results
| Initial avg. | 1.35fc |
|---|---|
| 90-min avg. | 0.95fc |
| Worst max:min | 22.5:1 |
| Battery bank | 12.43Ah |
| Walking surface area | 910ft² |
| Total initial fixture output | 13,300lm |
| Emitted flux per floor area | 14.62lm/ft² |
| Initial minimum | 0.16fc |
| Initial maximum | 3.6fc |
| Initial max / min | 22.5:1 |
| 90-minute minimum | 0.11fc |
| 90-minute maximum | 2.52fc |
| 90-minute max / min | 22.5:1 |
| Inverter real load | 140W |
| Inverter apparent load | 180VA |
| Assumed fixture power factor | 0.778 |
| Estimated DC current | 6.63A |
| DC energy before derating | 238.64Wh |
NFPA 101 egress screen
- Initial mean · 1.35 / ≥ 1 fc · Within screen
- Initial minimum · 0.16 / ≥ 0.1 fc · Within screen
- 90-minute mean · 0.945 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0.112 / ≥ 0.06 fc · Within screen
- Initial max / min · 22.5 / ≤ 40 :1 · Within screen
- 90-minute max / min · 22.5 / ≤ 40 :1 · Within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.