Office exit corridor on 24 V

Check a corridor with a common emergency-output retention factor and compute the battery Ah from real AC load.

Path and initial readings
ft
ft
fc
fc
fc
Emergency circuit and inverter
lm/W
W
VA
×
Initial avg.
1.35fc
90-min avg.
0.95fc
Worst max:min
22.5:1
Battery bank
12.43Ah

Initial and 90-minute path light levels

Edit inputs ↓
Initial and 90-minute path light levelsEGRESS FLOOR LEVELSURVEY RANGESInitial surveyavg 1.35 fc90-minute surveyavg 0.95 fcPath 130 ft40:1 limitWorst uniformity22.5:1
Markers show the minimum, mean and maximum for the entered survey. The ranges do not assign values to specific points on the path.

NFPA 101 egress screen

Within screen
OutsideThresholdWithin
  • Initial mean1.35 / ≥ 1 fc within screen
  • Initial minimum0.16 / ≥ 0.1 fc within screen
  • 90-minute mean0.945 / ≥ 0.6 fc within screen
  • 90-minute minimum0.112 / ≥ 0.06 fc within screen
  • Initial max / min22.5 / ≤ 40 :1 within screen
  • 90-minute max / min22.5 / ≤ 40 :1 within screen

The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.

Additional readings
Walking surface area910ft²
Total initial fixture output13,300lm
Emitted flux per floor area14.62lm/ft²
Initial minimum0.16fc
Initial maximum3.6fc
Initial max / min22.5:1
90-minute minimum0.11fc
90-minute maximum2.52fc
90-minute max / min22.5:1
Inverter real load140W
Inverter apparent load180VA
Assumed fixture power factor0.778
Estimated DC current6.63A
DC energy before derating238.64Wh

Worked calculation

US customary results for the original preset.

  1. The initial average and minimum are 1.35 fc and 0.16 fc. The corresponding 90-minute values are 0.95 fc and 0.11 fc.
  2. The worst maximum-to-minimum ratio is 22.5:1 against the 40:1 limit.
  3. The inverter supplies 180 VA and 140 W. For 90 minutes, the estimated derated bank is 12.43 Ah.

Calculation method

Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.

NFPA 101 screening floors
Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
Uniformity at both times
Emax/Emin ≤ 40:1 · a zero minimum fails the screen
Inverter and battery
VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)

Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.