Warehouse egress on a 48 V bank
Model a long aisle with a higher-voltage battery bank and larger aging and temperature derating.
Inputs
View results ↑- Initial avg.
- 1.6fc
- 90-min avg.
- 1.02fc
- Worst max:min
- 23.7:1
- Battery bank
- 13.22Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Within screen- Initial mean1.6 / ≥ 1 fc within screen
- Initial minimum0.19 / ≥ 0.1 fc within screen
- 90-minute mean1.024 / ≥ 0.6 fc within screen
- 90-minute minimum0.122 / ≥ 0.06 fc within screen
- Initial max / min23.684 / ≤ 40 :1 within screen
- 90-minute max / min23.684 / ≤ 40 :1 within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 1,680ft² |
|---|---|
| Total initial fixture output | 25,840lm |
| Emitted flux per floor area | 15.38lm/ft² |
| Initial minimum | 0.19fc |
| Initial maximum | 4.5fc |
| Initial max / min | 23.68:1 |
| 90-minute minimum | 0.12fc |
| 90-minute maximum | 2.88fc |
| 90-minute max / min | 23.68:1 |
| Inverter real load | 272W |
| Inverter apparent load | 336VA |
| Assumed fixture power factor | 0.81 |
| Estimated DC current | 6.3A |
| DC energy before derating | 453.33Wh |
Worked calculation
US customary results for the original preset.
- The initial average and minimum are 1.6 fc and 0.19 fc. The corresponding 90-minute values are 1.02 fc and 0.12 fc.
- The worst maximum-to-minimum ratio is 23.7:1 against the 40:1 limit.
- The inverter supplies 336 VA and 272 W. For 90 minutes, the estimated derated bank is 13.22 Ah.
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗Warehouse egress on a 48 V bank
Inputs
| Egress path length | 210ft |
|---|---|
| Path clear width | 8ft |
| Initial average | 1.6fc |
| Initial minimum | 0.19fc |
| Initial maximum | 4.5fc |
| 90-minute readings | Apply output retention factor |
| End-of-discharge retention | 0.64 |
| Emergency fixtures | 16 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 17W |
| Apparent input per fixture | 21VA |
| Battery system voltage | 48 V DC |
| Inverter efficiency | 0.9 |
| Battery aging / temperature factor | 1.4× |
Results
| Initial avg. | 1.6fc |
|---|---|
| 90-min avg. | 1.02fc |
| Worst max:min | 23.7:1 |
| Battery bank | 13.22Ah |
| Walking surface area | 1,680ft² |
| Total initial fixture output | 25,840lm |
| Emitted flux per floor area | 15.38lm/ft² |
| Initial minimum | 0.19fc |
| Initial maximum | 4.5fc |
| Initial max / min | 23.68:1 |
| 90-minute minimum | 0.12fc |
| 90-minute maximum | 2.88fc |
| 90-minute max / min | 23.68:1 |
| Inverter real load | 272W |
| Inverter apparent load | 336VA |
| Assumed fixture power factor | 0.81 |
| Estimated DC current | 6.3A |
| DC energy before derating | 453.33Wh |
NFPA 101 egress screen
- Initial mean · 1.6 / ≥ 1 fc · Within screen
- Initial minimum · 0.19 / ≥ 0.1 fc · Within screen
- 90-minute mean · 1.024 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0.122 / ≥ 0.06 fc · Within screen
- Initial max / min · 23.684 / ≤ 40 :1 · Within screen
- 90-minute max / min · 23.684 / ≤ 40 :1 · Within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.