Installed flow characteristic
Control valve authority calculator
Compare inherent and installed flow curves for linear, equal-percentage and quick-opening trims at the selected valve travel.
Inputs
Results
Edit inputs- Authority a
- 0.3
- Inherent flow
- 17.2%
- Installed flow
- 30.4%
- Flow shift
- 13.2pp
Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 0.3 |
|---|---|
| Inherent flow fraction | 17.2 % |
| Installed flow fraction | 30.37 % |
| Installed minus inherent | 13.17 pp |
| Total available pressure | 40 psi |
| Valve share at selected lift | 93.5 % |
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references