Installed flow characteristic
Linear trim in a high-authority loop
The valve takes most of the fully open pressure budget in a compact process loop.
Inputs
Results
Edit inputs- Authority a
- 0.8
- Inherent flow
- 40%
- Installed flow
- 43.9%
- Flow shift
- 3.9pp
Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 0.8 |
|---|---|
| Inherent flow fraction | 40 % |
| Installed flow fraction | 43.85 % |
| Installed minus inherent | 3.85 pp |
| Total available pressure | 30 psi |
| Valve share at selected lift | 96.2 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Allocate full-open pressure0.8
- Read the selected trim40 %
- Apply system resistance43.85 %
Installed flow tracks inherent flow more closely as authority rises. Change lift to see where the curves separate most.
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references