Installed flow characteristic

Linear trim in a high-authority loop

The valve takes most of the fully open pressure budget in a compact process loop.

Inputs

Full-open duty
Valve characteristic
Authority a
0.8
Inherent flow
40%
Installed flow
43.9%
Flow shift
3.9pp
Authority curve available

Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.

Inherent vs installed flow

Inherent vs installed flowEach curve is normalized to fully open flow. Markers show the selected stem lift.0%50%100%0%STEM LIFT100%INHERENTINSTALLEDAUTHORITY0.8STEM LIFT40 %FLOW SHIFT3.9 pp
Each curve is normalized to fully open flow. Markers show the selected stem lift.

All calculated values
Full-open valve authority0.8
Inherent flow fraction40 %
Installed flow fraction43.85 %
Installed minus inherent3.85 pp
Total available pressure30 psi
Valve share at selected lift96.2 %

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Allocate full-open pressure0.8
  2. Read the selected trim40 %
  3. Apply system resistance43.85 %

Installed flow tracks inherent flow more closely as authority rises. Change lift to see where the curves separate most.

Model and limits

Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.

Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.

View equations and references

Worked examples