Installed flow characteristic
Fully open valve normalization
An engineer checks the reference condition for a plant flow-control loop at full travel.
Inputs
Results
Edit inputs- Authority a
- 0.25
- Inherent flow
- 100%
- Installed flow
- 100%
- Flow shift
- 0pp
Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 0.25 |
|---|---|
| Inherent flow fraction | 100 % |
| Installed flow fraction | 100 % |
| Installed minus inherent | 0 pp |
| Total available pressure | 36 psi |
| Valve share at selected lift | 25 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Allocate full-open pressure0.25
- Read the selected trim100 %
- Apply system resistance100 %
Both curves reach 100% full-open flow. At that point the valve share of pressure equals the full-open authority.
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references