Installed flow characteristic
Quick-opening bypass at quarter travel
A quick-opening bypass serves batch circulation and spends little time near full travel.
Inputs
Results
Edit inputs- Authority a
- 0.2
- Inherent flow
- 50%
- Installed flow
- 79.1%
- Flow shift
- 29.1pp
The installed curve can rise much faster than the inherent trim curve. Review controllability over the duty range.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 0.2 |
|---|---|
| Inherent flow fraction | 50 % |
| Installed flow fraction | 79.06 % |
| Installed minus inherent | 29.06 pp |
| Total available pressure | 40 psi |
| Valve share at selected lift | 50 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Allocate full-open pressure0.2
- Read the selected trim50 %
- Apply system resistance79.06 %
A small change in lift can already deliver substantial flow. Use the OEM characteristic to evaluate low-travel control.
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references