Installed flow characteristic

Quick-opening bypass at quarter travel

A quick-opening bypass serves batch circulation and spends little time near full travel.

Inputs

Full-open duty
Valve characteristic
Authority a
0.2
Inherent flow
50%
Installed flow
79.1%
Flow shift
29.1pp
Low full-open authority

The installed curve can rise much faster than the inherent trim curve. Review controllability over the duty range.

Inherent vs installed flow

Inherent vs installed flowEach curve is normalized to fully open flow. Markers show the selected stem lift.0%50%100%0%STEM LIFT100%INHERENTINSTALLEDAUTHORITY0.2STEM LIFT25 %FLOW SHIFT29.1 pp
Each curve is normalized to fully open flow. Markers show the selected stem lift.

All calculated values
Full-open valve authority0.2
Inherent flow fraction50 %
Installed flow fraction79.06 %
Installed minus inherent29.06 pp
Total available pressure40 psi
Valve share at selected lift50 %

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Allocate full-open pressure0.2
  2. Read the selected trim50 %
  3. Apply system resistance79.06 %

A small change in lift can already deliver substantial flow. Use the OEM characteristic to evaluate low-travel control.

Model and limits

Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.

Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.

View equations and references

Worked examples