Installed flow characteristic

Equal-percentage trim at low authority

A long distribution circuit takes most of the available pressure when the valve is open.

Inputs

Full-open duty
Valve characteristic
Authority a
0.125
Inherent flow
33.4%
Installed flow
70.8%
Flow shift
37.4pp
Low full-open authority

The installed curve can rise much faster than the inherent trim curve. Review controllability over the duty range.

Inherent vs installed flow

Inherent vs installed flowEach curve is normalized to fully open flow. Markers show the selected stem lift.0%50%100%0%STEM LIFT100%INHERENTINSTALLEDAUTHORITY0.125STEM LIFT72 %FLOW SHIFT37.4 pp
Each curve is normalized to fully open flow. Markers show the selected stem lift.

All calculated values
Full-open valve authority0.125
Inherent flow fraction33.44 %
Installed flow fraction70.84 %
Installed minus inherent37.4 pp
Total available pressure40 psi
Valve share at selected lift56.1 %

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Allocate full-open pressure0.125
  2. Read the selected trim33.44 %
  3. Apply system resistance70.84 %

The installed curve rises above the inherent Cv curve. Compare the process gain near the actual operating travel.

Model and limits

Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.

Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.

View equations and references

Worked examples