Installed flow characteristic

Control valve authority calculator

Compare inherent and installed flow curves for linear, equal-percentage and quick-opening trims at the selected valve travel.

Inputs

Full-open duty
Valve characteristic
Authority a
0.3
Inherent flow
17.2%
Installed flow
30.4%
Flow shift
13.2pp
Authority curve available

Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.

Inherent vs installed flow

Inherent vs installed flowEach curve is normalized to fully open flow. Markers show the selected stem lift.0%50%100%0%STEM LIFT100%INHERENTINSTALLEDAUTHORITY0.3STEM LIFT55 %FLOW SHIFT13.2 pp
Each curve is normalized to fully open flow. Markers show the selected stem lift.

All calculated values
Full-open valve authority0.3
Inherent flow fraction17.2 %
Installed flow fraction30.37 %
Installed minus inherent13.17 pp
Total available pressure40 psi
Valve share at selected lift93.5 %

Model and limits

Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.

Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.

View equations and references

Worked examples