ASME B31.3 flexibility screen
Pipe thermal expansion and loop calculator
Estimate pipe growth or contraction and screen L-bend, Z-bend or U-loop leg length against the entered allowable displacement stress range.
Inputs
Results
Edit inputs- Movement ΔL
- 2.69in
- Minimum leg
- 13.52ft
- Leg stress
- 16.24ksi
- Stress margin
- 3.76ksi
The provided leg meets the entered stress range in the guided-cantilever screen.
Thermal movement and routing
All calculated values
| Temperature change ΔT | 280 °F |
|---|---|
| Signed run movement ΔL | 2.688 in |
| Motion assigned to each leg | 1.344 in |
| Minimum flexing leg | 13.518 ft |
| Width at minimum U-loop height | 8.111 ft |
| Width at provided U-loop height | 9 ft |
| Screened displacement stress | 16.24 ksi |
| Available stress range | 3.76 ksi |
| Allowable range used | 81.2 % |
| Nominal elastic modulus | 29.01 Mpsi |
| Linear expansion coefficient | 0.000012 1/°C |
Model and limits
Use the length between effective anchors and the install-to-operating temperature difference. The guided-cantilever screen assigns the full displacement to a single L-leg or shares it equally across the two idealized legs of a Z-offset or U-loop.
Use a project-approved allowable displacement stress range Sₐ. Representative moduli and coefficients are constant over the entered temperature range. Confirm temperature-dependent properties, anchor loads, direction of movement, elbow flexibility, fatigue cycles and stress intensification using the governing B31.3 edition and a pipe stress analysis. U-loop width is a layout estimate from the entered aspect ratio.
View equations and references