ASME B31.3 flexibility screen

CPVC process-water expansion loop

A CPVC process-water line sees a 40 °C temperature increase after commissioning.

Inputs

Thermal duty
Flexibility screen
Movement ΔL
78.08mm
Minimum leg
2.89m
Leg stress
3.48MPa
Stress margin
0.52MPa
Leg within entered Sₐ

The provided leg meets the entered stress range in the guided-cantilever screen. Confirm CPVC temperature and long-term modulus with the manufacturer.

Thermal movement and routing

Thermal movement and routingArrows indicate the direction of thermal movement. The routed legs and dimensions represent the selected layout.RUN ΔL78.08 mmLOOP WIDTH2.48 mWHFLEXING PIPEMIN. LEG2.89 mPROVIDED LEG3.1 mSTRESS MARGIN0.52 MPa
Arrows indicate the direction of thermal movement. The routed legs and dimensions represent the selected layout.

All calculated values
Temperature change ΔT40 °C
Signed run movement ΔL78.08 mm
Motion assigned to each leg39.04 mm
Minimum flexing leg2.893 m
Width at minimum U-loop height2.314 m
Width at provided U-loop height2.48 m
Screened displacement stress3.48 MPa
Available stress range0.52 MPa
Allowable range used87.1 %
Nominal elastic modulus2.5 GPa
Linear expansion coefficient0.000061 1/°C

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Calculate signed pipe movement78.08 mm
  2. Find the flexing leg length2.893 m
  3. Compare with available stress range0.52 MPa

CPVC grows more per degree than steel. Verify the permissible temperature, long-term modulus and anchor loads with the manufacturer.

Model and limits

Use the length between effective anchors and the install-to-operating temperature difference. The guided-cantilever screen assigns the full displacement to a single L-leg or shares it equally across the two idealized legs of a Z-offset or U-loop.

Use a project-approved allowable displacement stress range Sₐ. Representative moduli and coefficients are constant over the entered temperature range. Confirm temperature-dependent properties, anchor loads, direction of movement, elbow flexibility, fatigue cycles and stress intensification using the governing B31.3 edition and a pipe stress analysis. U-loop width is a layout estimate from the entered aspect ratio.

View equations and references

Worked examples