Gutter runoff from a 900 ft² gable half
One eave receives 900 ft² of projected roof at 4:12. A 4 in/hr storm and a 36 ft run drive the first downspout estimate.
Worked calculation
Use the area contributing to this one eave. The projected flow is about 37.4 gal/min. With the pitch allowance and outlet limits, two downspouts serve the reach.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Estimated gutter width
- Downspouts for selected layout
- Adjusted drainage area
- Pitch allowance
- Peak runoff from projected area
- Peak runoff, alternate units
- Sizing flow with pitch allowance
- Sizing flow per outlet
- Average eave length per outlet
- 5 in / 127 mm reference
- 6 in / 152 mm reference
- Selected outlet assembly capacity
- 2 × 3 in / 51 × 76 mm leader minimum
- 3 × 4 in / 76 × 102 mm leader minimum
- 4 in / 102 mm round leader minimum
Worksheet inputs US customary
- Projected area draining to this gutter
- 900 ft²
- Contributing roof pitch
- 4:12
- Peak rainfall intensity
- 4 in/hr
- Continuous eave run
- 36 ft
- Maximum length served per outlet
- 35 ft
- Gutter profile
- K-style
- Downspout profile
- 2 × 3 in rectangular
- 5 in / 127 mm gutter capacity
- 0 US gal/min
- 6 in / 152 mm gutter capacity
- 0 US gal/min
- Selected outlet assembly capacity
- 0 US gal/min
Apply this example to your roof
Half-round defaults use the 2021 IPC semicircular reference at 1/8 in/ft. K-style defaults of 60 and 90 gal/min and leader assembly defaults of 30, 60 and 90 gal/min are screening assumptions. Replace them with documented ratings for your slope, outlets and profiles. Check concentrated valley flow, walls that contribute runoff and overflow paths.
Frequently asked questions
Should both halves of the 900 ft² gable example enter one eave?
Enter the half that drains to this eave. Evaluate the opposite half separately unless it drains to the same gutter.
What drives the two outlet estimate on the 36-foot run?
Both the 35 ft service limit and the 30 gal/min screening outlet capacity require two outlets here.