Split eave reaches when the gutter limits flow
A shop roof drains 1,500 ft² into profile sections rated at 25 and 40 gal/min. Its specified outlet assembly can handle 110 gal/min.
Worked calculation
Estimated sizing flow is about 137.1 gal/min. Although two outlets would meet the spacing and outlet checks, each 6-inch reach can handle only 40 gal/min, so the screen calls for four.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Estimated gutter width
- Downspouts for selected layout
- Adjusted drainage area
- Pitch allowance
- Peak runoff from projected area
- Peak runoff, alternate units
- Sizing flow with pitch allowance
- Sizing flow per outlet
- Average eave length per outlet
- 5 in / 127 mm reference
- 6 in / 152 mm reference
- Selected outlet assembly capacity
- 2 × 3 in / 51 × 76 mm leader minimum
- 3 × 4 in / 76 × 102 mm leader minimum
- 4 in / 102 mm round leader minimum
- Gutter capacity requires more equally loaded reaches than downspout capacity and spacing alone.
Worksheet inputs US customary
- Projected area draining to this gutter
- 1,500 ft²
- Contributing roof pitch
- 6:12
- Peak rainfall intensity
- 8 in/hr
- Continuous eave run
- 52 ft
- Maximum length served per outlet
- 35 ft
- Gutter profile
- K-style
- Downspout profile
- 4 in round
- 5 in / 127 mm gutter capacity
- 25 US gal/min
- 6 in / 152 mm gutter capacity
- 40 US gal/min
- Selected outlet assembly capacity
- 110 US gal/min
Apply this example to your roof
Half-round defaults use the 2021 IPC semicircular reference at 1/8 in/ft. K-style defaults of 60 and 90 gal/min and leader assembly defaults of 30, 60 and 90 gal/min are screening assumptions. Replace them with documented ratings for your slope, outlets and profiles. Check concentrated valley flow, walls that contribute runoff and overflow paths.
Frequently asked questions
Why can a large leader fail to reduce the number of shop reaches?
The gutter can reach its own flow limit first. Each selected reach needs a gutter and outlet that both pass the estimated flow.
Where do I enter the supplier’s 40 gal/min capacity?
Open Capacity overrides and use the 6-inch profile field. Supply a rating at the actual installation slope and geometry.