Split eave reaches when the gutter limits flow

A shop roof drains 1,500 ft² into profile sections rated at 25 and 40 gal/min. Its specified outlet assembly can handle 110 gal/min.

Worked calculation

Estimated sizing flow is about 137.1 gal/min. Although two outlets would meet the spacing and outlet checks, each 6-inch reach can handle only 40 gal/min, so the screen calls for four.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Contributing roof and storm
ft²
:12
Gutter and outlets
ft
ft
Capacity overrides
US gal/min Zero uses the profile’s reference capacity.
US gal/min Enter the manufacturer’s flow for your actual slope and run.
US gal/min Zero uses the screening value for the selected profile.

Results

Live

Gutter reaches and downspout flowEstimated gutter width 6 in. Downspouts for selected layout 4. K-STYLE GUTTER6 in nominal4 downspouts34.29 US gal/min each13 ft eave length per outlet
Gutter reaches and downspout flow Schematic
Adjusted drainage area
1,650 ft²
Pitch allowance
1.1×
Peak runoff from projected area
124.68 US gal/min
Peak runoff, alternate units
0.2778 ft³/s
Sizing flow with pitch allowance
137.14 US gal/min
Sizing flow per outlet
34.29 US gal/min
Average eave length per outlet
13 ft
5 in / 127 mm reference
25 US gal/min
6 in / 152 mm reference
40 US gal/min
Selected outlet assembly capacity
110 US gal/min
2 × 3 in / 51 × 76 mm leader minimum
5
3 × 4 in / 76 × 102 mm leader minimum
3
4 in / 102 mm round leader minimum
2
  • Gutter capacity requires more equally loaded reaches than downspout capacity and spacing alone.

Apply this example to your roof

Half-round defaults use the 2021 IPC semicircular reference at 1/8 in/ft. K-style defaults of 60 and 90 gal/min and leader assembly defaults of 30, 60 and 90 gal/min are screening assumptions. Replace them with documented ratings for your slope, outlets and profiles. Check concentrated valley flow, walls that contribute runoff and overflow paths.

Read the calculator method and references

Frequently asked questions

Why can a large leader fail to reduce the number of shop reaches?

The gutter can reach its own flow limit first. Each selected reach needs a gutter and outlet that both pass the estimated flow.

Where do I enter the supplier’s 40 gal/min capacity?

Open Capacity overrides and use the 6-inch profile field. Supply a rating at the actual installation slope and geometry.