Half-round gutter for a copper retrofit
A 24 ft historic eave is being fitted with half-round gutter and a round leader sized for a projected roof area of 1,000 ft².
Worked calculation
At 8 in/hr, roughly 83.1 gal/min reaches the gutter. The 5-inch semicircular reference is 74 gal/min, so this screen suggests 6 inches at the reference slope.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Estimated gutter width
- Downspouts for selected layout
- Adjusted drainage area
- Pitch allowance
- Peak runoff from projected area
- Peak runoff, alternate units
- Sizing flow with pitch allowance
- Sizing flow per outlet
- Average eave length per outlet
- 5 in / 127 mm reference
- 6 in / 152 mm reference
- Selected outlet assembly capacity
- 2 × 3 in / 51 × 76 mm leader minimum
- 3 × 4 in / 76 × 102 mm leader minimum
- 4 in / 102 mm round leader minimum
Worksheet inputs US customary
- Projected area draining to this gutter
- 1,000 ft²
- Contributing roof pitch
- 3:12
- Peak rainfall intensity
- 8 in/hr
- Continuous eave run
- 24 ft
- Maximum length served per outlet
- 35 ft
- Gutter profile
- Half-round
- Downspout profile
- 4 in round
- 5 in / 127 mm gutter capacity
- 0 US gal/min
- 6 in / 152 mm gutter capacity
- 0 US gal/min
- Selected outlet assembly capacity
- 0 US gal/min
Apply this example to your roof
Half-round defaults use the 2021 IPC semicircular reference at 1/8 in/ft. K-style defaults of 60 and 90 gal/min and leader assembly defaults of 30, 60 and 90 gal/min are screening assumptions. Replace them with documented ratings for your slope, outlets and profiles. Check concentrated valley flow, walls that contribute runoff and overflow paths.
Frequently asked questions
Which half-round gutter reference slope does the copper example use?
The default reference is the 2021 IPC semicircular table at 1/8 inch per foot. Confirm the actual profile and slope.
Why does the half-round case keep a single round downspout?
The eave is within the spacing input and its sizing flow is below the selected assembly’s 90 gal/min screening value.