Valley-fed eave with a restricted outlet

A valley drains a combined 650 ft² projection into one eave. A tested outlet fitting is rated for 25 gal/min.

Worked calculation

With a 1.20 pitch allowance, the sizing flow is about 97.2 gal/min. Four evenly loaded outlets cover the aggregate rate. The valley may need a separate local overflow check.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Contributing roof and storm
ft²
:12
Gutter and outlets
ft
ft
Capacity overrides
US gal/min Zero uses the profile’s reference capacity.
US gal/min Enter the manufacturer’s flow for your actual slope and run.
US gal/min Zero uses the screening value for the selected profile.

Results

Live

Gutter reaches and downspout flowEstimated gutter width 5 in. Downspouts for selected layout 4. K-STYLE GUTTER5 in nominal4 downspouts24.31 US gal/min each9 ft eave length per outlet
Gutter reaches and downspout flow Schematic
Adjusted drainage area
780 ft²
Pitch allowance
1.2×
Peak runoff from projected area
81.04 US gal/min
Peak runoff, alternate units
0.1806 ft³/s
Sizing flow with pitch allowance
97.25 US gal/min
Sizing flow per outlet
24.31 US gal/min
Average eave length per outlet
9 ft
5 in / 127 mm reference
60 US gal/min
6 in / 152 mm reference
90 US gal/min
Selected outlet assembly capacity
25 US gal/min
2 × 3 in / 51 × 76 mm leader minimum
4
3 × 4 in / 76 × 102 mm leader minimum
2
4 in / 102 mm round leader minimum
2

Apply this example to your roof

Half-round defaults use the 2021 IPC semicircular reference at 1/8 in/ft. K-style defaults of 60 and 90 gal/min and leader assembly defaults of 30, 60 and 90 gal/min are screening assumptions. Replace them with documented ratings for your slope, outlets and profiles. Check concentrated valley flow, walls that contribute runoff and overflow paths.

Read the calculator method and references

Frequently asked questions

Why use 25 gal/min for a nominal 3 × 4 valley downspout?

The measured outlet fitting controls the assumed assembly flow. Enter the lower documented capacity for the connector and leader together.

Does splitting a valley-fed gutter guarantee equal loading at four outlets?

Check the valley discharge point and flow path. The model’s four-way split assumes an even allocation across reaches.