Flat Roof Tapered Insulation, Crickets & R-Value Calculator

Calculate thick and thin ends, net drain slope, thermal resistance, board volume and optional cricket size.

Inputs

Units
Drainage zone
ft²
ft
in/ft Use a negative value when the deck falls away from the drain.
in
Optional diamond cricket
ft Set the length to zero to omit the cricket.
ft
in/ft

Results

Live

Tapered insulation section and cricketThick end of main taper 8 in. Total insulation volume 8,018 board ft. INSULATION SECTION8,018 board ft totalThick 8 inDrain 2 inRun 24 ftNet slope 0.25 in/ftCricket +1.5 in
Tapered insulation section and cricket Schematic
Insulation rise
6 in
Net surface slope toward drain
0.25 in/ft
Net surface fall to drain
6 in
Average main-taper thickness
5 in
Thermal resistance per thickness
5.7 R/in
Thin-end insulation R-value
11.4 h·ft²·°F/Btu
Arithmetic average insulation R-value
28.5 h·ft²·°F/Btu
Idealized effective insulation R-value
24.67 h·ft²·°F/Btu
Main taper volume
8,000 board ft
Cricket projected area
36 ft²
Cricket add-on peak rise
1.5 in
Cricket add-on volume
18 board ft
Cricket center-to-tip ridge slope
0.25 in/ft

Build slope while tracking roof buildup

  1. Multiply the board slope by the horizontal run to get the change in thickness. Add the signed deck slope to the board slope for the slope of the finished surface.
  2. For a rectangular zone with uniform taper, the average thickness is halfway between the ends. Multiply by projected area for board feet, or convert to cubic meters. Effective insulation R models parallel heat paths through the tapered section.
  3. A symmetric diamond cricket has half the product of its length and width in plan area. Its peak rise is cross-slope × half-width. The idealized add-on volume is plan area × peak rise ÷ 3.

Verify roof assembly slope and thermal requirements, low spots, flashing clearance, tapered board layouts and secondary drainage. The R-value is for the modeled insulation. The arithmetic average does not describe the thin-end R-value.

References

Frequently asked questions

What is a board foot of tapered roof insulation?

One board foot is one square foot of insulation one inch thick. Multiply the average thickness in inches by the projected area in square feet for a uniform taper.

Why can a tapered roof still pond after insulation is added?

An adverse deck slope, deflection, drain elevations and obstructions can reduce the finished slope or create local low spots. Check the drainage plan and existing elevations.

How is effective R different from average R on a tapered roof?

Effective R averages heat transfer through the varying thicknesses. Arithmetic R uses the average thickness. The effective calculation gives greater influence to thin sections.