7 bar g to an atmospheric receiver

The Spirax Sarco tutorial uses 250 kg/h of saturated condensate at 7 bar g discharging to atmosphere.

Inputs

lb/hr
psig
psig
%
%
Percentage of post-flash liquid flow.
°F
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
USD/1,000 gal
Flash vessel phase separation
Flash vessel phase separationFLASH 13.4 %. FLASH USED 73.8 lb/hr. RETURN FLOW 477.3 lb/hr. YEAR SAVINGS 10.95K USD/yrFLASH13.4%FLASH USED73.8lb/hrRETURN FLOW477.3lb/hrYEAR SAVINGS10.95KUSD/yrFLASH VESSEL0 psigCONDENSATE IN101.53 psigFLASH VAPORLIQUID RETURN86.6% of inletVapor share of inlet mass13.4% flash0%Liquid + vapor = inlet100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Flash steam fraction
13.4%
Flash steam generated
73.8lb/hr
Flash steam used
73.8lb/hr
Post-flash liquid
477.3lb/hr
Condensate returned
477.3lb/hr
Original inlet mass returned
86.6%
Inlet heat recovered by liquid return
45.52%
Flash latent heat credit
71,637.87Btu/h
Return sensible heat credit
68,739.93Btu/h
Source liquid enthalpy
310.11Btu/lb
Receiver liquid enthalpy
180.13Btu/lb
Receiver latent heat
970.14Btu/lb
Annual fuel energy avoided
1,112.8MMBtu/yr
Annual fuel savings
9,458USD/yr
Annual water and treatment savings
1,487USD/yr
Combined annual savings
10,945USD/yr

Check the original case

Compare the computed flash fraction with the tutorial’s rounded 13.4% and approximately 33.5 kg/h of flash.

  • Flash steam fraction13.4 %
  • Flash steam used73.8 lb/hr
  • Condensate returned477.3 lb/hr
  • Combined annual savings10,945 USD/yr

Formulas and assumptions

Isenthalpic flash

f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f

The inlet is saturated liquid at P₁. Flow leaves the receiver as saturated vapor and saturated liquid at P₂.

Heat credit

Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup)

The liquid credit percentage divides returned heat by all inlet sensible heat above cold make-up. Vapor credit uses latent heat, with no liquid return assumed from the vapor user.

Annual savings

Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]

Water and treatment savings apply to returned liquid at an accounting density of 1,000 kg/m³. Enter the combined water and treatment tariff.

Worked examples

Open a case to edit its inputs.