7 bar g to an atmospheric receiver
The Spirax Sarco tutorial uses 250 kg/h of saturated condensate at 7 bar g discharging to atmosphere.
Inputs
Inputs
- High-pressure condensate
- 551.2 lb/hr
- Source pressure P₁
- 101.53 psig
- Receiver pressure P₂
- 0 psig
- Flash steam utilization
- 100 %
- Liquid condensate returned
- 100 %
- Cold make-up temperature
- 68 °F
- Boiler efficiency
- 82 %
- Annual operating time
- 6,500 h/yr
- Currency
- USD
- Energy price
- 8.5 USD/MMBtu
- Water + treatment price
- 4 USD/1,000 gal
Calculation results
- Flash steam fraction
- 13.4%
- Flash steam generated
- 73.8lb/hr
- Flash steam used
- 73.8lb/hr
- Post-flash liquid
- 477.3lb/hr
- Condensate returned
- 477.3lb/hr
- Original inlet mass returned
- 86.6%
- Inlet heat recovered by liquid return
- 45.52%
- Flash latent heat credit
- 71,637.87Btu/h
- Return sensible heat credit
- 68,739.93Btu/h
- Source liquid enthalpy
- 310.11Btu/lb
- Receiver liquid enthalpy
- 180.13Btu/lb
- Receiver latent heat
- 970.14Btu/lb
- Annual fuel energy avoided
- 1,112.8MMBtu/yr
- Annual fuel savings
- 9,458USD/yr
- Annual water and treatment savings
- 1,487USD/yr
- Combined annual savings
- 10,945USD/yr
Calculation basis
- Isenthalpic flash
f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f - Heat credit
Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup) - Annual savings
Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]
Check the original case
Compare the computed flash fraction with the tutorial’s rounded 13.4% and approximately 33.5 kg/h of flash.
- Flash steam fraction13.4 %
- Flash steam used73.8 lb/hr
- Condensate returned477.3 lb/hr
- Combined annual savings10,945 USD/yr
Formulas and assumptions
Isenthalpic flash
f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f
The inlet is saturated liquid at P₁. Flow leaves the receiver as saturated vapor and saturated liquid at P₂.
Heat credit
Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup)
The liquid credit percentage divides returned heat by all inlet sensible heat above cold make-up. Vapor credit uses latent heat, with no liquid return assumed from the vapor user.
Annual savings
Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]
Water and treatment savings apply to returned liquid at an accounting density of 1,000 kg/m³. Enter the combined water and treatment tariff.
Worked examples
Open a case to edit its inputs.