Vented flash with liquid-only recovery

A receiver vents all flash steam but pumps part of the remaining liquid back to the boiler plant.

Inputs

lb/hr
psig
psig
%
%
Percentage of post-flash liquid flow.
°F
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
USD/1,000 gal
Flash vessel phase separation
Flash vessel phase separationFLASH 16.85 %. FLASH USED 0 lb/hr. RETURN FLOW 3,592 lb/hr. YEAR SAVINGS 46.05K USD/yrFLASH16.85%FLASH USED0lb/hrRETURN FLOW3,592lb/hrYEAR SAVINGS46.05KUSD/yrFLASH VESSEL0 psigCONDENSATE IN160 psigFLASH VAPORLIQUID RETURN59.87% of inletVapor share of inlet mass16.85% flash0%Liquid + vapor = inlet100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Flash steam fraction
16.85%
Flash steam generated
1,011.1lb/hr
Flash steam used
0lb/hr
Post-flash liquid
4,988.9lb/hr
Condensate returned
3,592lb/hr
Original inlet mass returned
59.87%
Inlet heat recovered by liquid return
28.04%
Flash latent heat credit
0Btu/h
Return sensible heat credit
517,302.74Btu/h
Source liquid enthalpy
343.62Btu/lb
Receiver liquid enthalpy
180.13Btu/lb
Receiver latent heat
970.14Btu/lb
Annual fuel energy avoided
4,100.6MMBtu/yr
Annual fuel savings
34,855USD/yr
Annual water and treatment savings
11,191USD/yr
Combined annual savings
46,046USD/yr

Check the original case

Flash latent heat credit is zero. Both sensible heat and water savings come from returned liquid.

  • Flash steam fraction16.85 %
  • Flash steam used0 lb/hr
  • Condensate returned3,592 lb/hr
  • Combined annual savings46,046 USD/yr

Formulas and assumptions

Isenthalpic flash

f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f

The inlet is saturated liquid at P₁. Flow leaves the receiver as saturated vapor and saturated liquid at P₂.

Heat credit

Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup)

The liquid credit percentage divides returned heat by all inlet sensible heat above cold make-up. Vapor credit uses latent heat, with no liquid return assumed from the vapor user.

Annual savings

Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]

Water and treatment savings apply to returned liquid at an accounting density of 1,000 kg/m³. Enter the combined water and treatment tariff.

Worked examples

Open a case to edit its inputs.