125 psig condensate to 10 psig

A plant sends 3,500 lb/hr of saturated condensate from 125 psig to a flash receiver at 10 psig.

Inputs

lb/hr
psig
psig
%
%
Percentage of post-flash liquid flow.
°F
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
USD/1,000 gal
Flash vessel phase separation
Flash vessel phase separationFLASH 12.28 %. FLASH USED 386.9 lb/hr. RETURN FLOW 2,609.6 lb/hr. YEAR SAVINGS 63.15K USD/yrFLASH12.28%FLASH USED386.9lb/hrRETURN FLOW2,609.6lb/hrYEAR SAVINGS63.15KUSD/yrFLASH VESSEL10 psigCONDENSATE IN125 psigFLASH VAPORLIQUID RETURN74.56% of inletVapor share of inlet mass12.28% flash0%Liquid + vapor = inlet100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Flash steam fraction
12.28%
Flash steam generated
429.9lb/hr
Flash steam used
386.9lb/hr
Post-flash liquid
3,070.1lb/hr
Condensate returned
2,609.6lb/hr
Original inlet mass returned
74.56%
Inlet heat recovered by liquid return
44.34%
Flash latent heat credit
368,521.93Btu/h
Return sensible heat credit
448,073.09Btu/h
Source liquid enthalpy
324.81Btu/lb
Receiver liquid enthalpy
207.82Btu/lb
Receiver latent heat
952.49Btu/lb
Annual fuel energy avoided
6,473MMBtu/yr
Annual fuel savings
55,021USD/yr
Annual water and treatment savings
8,130USD/yr
Combined annual savings
63,151USD/yr

Check the original case

Add generated vapor and post-flash liquid to recover the inlet mass. The utilized vapor can be lower than the generated vapor.

  • Flash steam fraction12.28 %
  • Flash steam used386.9 lb/hr
  • Condensate returned2,609.6 lb/hr
  • Combined annual savings63,151 USD/yr

Formulas and assumptions

Isenthalpic flash

f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f

The inlet is saturated liquid at P₁. Flow leaves the receiver as saturated vapor and saturated liquid at P₂.

Heat credit

Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup)

The liquid credit percentage divides returned heat by all inlet sensible heat above cold make-up. Vapor credit uses latent heat, with no liquid return assumed from the vapor user.

Annual savings

Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]

Water and treatment savings apply to returned liquid at an accounting density of 1,000 kg/m³. Enter the combined water and treatment tariff.

Worked examples

Open a case to edit its inputs.