Small pressure drop on a hot return
A hot condensate loop returns 5,000 kg/h across a 0.5 bar pressure difference.
Inputs
Inputs
- High-pressure condensate
- 11,023.1 lb/hr
- Source pressure P₁
- 87.02 psig
- Receiver pressure P₂
- 79.77 psig
- Flash steam utilization
- 90 %
- Liquid condensate returned
- 95 %
- Cold make-up temperature
- 86 °F
- Boiler efficiency
- 82 %
- Annual operating time
- 6,500 h/yr
- Currency
- GBP
- Energy price
- 9.496 GBP/MMBtu
- Water + treatment price
- 4 GBP/1,000 gal
Calculation results
- Flash steam fraction
- 0.62%
- Flash steam generated
- 68.6lb/hr
- Flash steam used
- 61.7lb/hr
- Post-flash liquid
- 10,954.5lb/hr
- Condensate returned
- 10,406.8lb/hr
- Original inlet mass returned
- 94.41%
- Inlet heat recovered by liquid return
- 92.28%
- Flash latent heat credit
- 55,056.42Btu/h
- Return sensible heat credit
- 2,499,846.69Btu/h
- Source liquid enthalpy
- 299.86Btu/lb
- Receiver liquid enthalpy
- 294.31Btu/lb
- Receiver latent heat
- 892.14Btu/lb
- Annual fuel energy avoided
- 20,252.3MMBtu/yr
- Annual fuel savings
- 192,306GBP/yr
- Annual water and treatment savings
- 32,422GBP/yr
- Combined annual savings
- 224,728GBP/yr
Calculation basis
- Isenthalpic flash
f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f - Heat credit
Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup) - Annual savings
Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]
Check the original case
A small flash percentage leaves most mass and recoverable heat in the liquid.
- Flash steam fraction0.62 %
- Flash steam used61.7 lb/hr
- Condensate returned10,406.8 lb/hr
- Combined annual savings224,728 GBP/yr
Formulas and assumptions
Isenthalpic flash
f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f
The inlet is saturated liquid at P₁. Flow leaves the receiver as saturated vapor and saturated liquid at P₂.
Heat credit
Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup)
The liquid credit percentage divides returned heat by all inlet sensible heat above cold make-up. Vapor credit uses latent heat, with no liquid return assumed from the vapor user.
Annual savings
Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]
Water and treatment savings apply to returned liquid at an accounting density of 1,000 kg/m³. Enter the combined water and treatment tariff.
Worked examples
Open a case to edit its inputs.