Vented flash with liquid-only recovery
A receiver vents all flash steam but pumps part of the remaining liquid back to the boiler plant.
Inputs
Inputs
- High-pressure condensate
- 6,000 lb/hr
- Source pressure P₁
- 160 psig
- Receiver pressure P₂
- 0 psig
- Flash steam utilization
- 0 %
- Liquid condensate returned
- 72 %
- Cold make-up temperature
- 68 °F
- Boiler efficiency
- 82 %
- Annual operating time
- 6,500 h/yr
- Currency
- USD
- Energy price
- 8.5 USD/MMBtu
- Water + treatment price
- 4 USD/1,000 gal
Calculation results
- Flash steam fraction
- 16.85%
- Flash steam generated
- 1,011.1lb/hr
- Flash steam used
- 0lb/hr
- Post-flash liquid
- 4,988.9lb/hr
- Condensate returned
- 3,592lb/hr
- Original inlet mass returned
- 59.87%
- Inlet heat recovered by liquid return
- 28.04%
- Flash latent heat credit
- 0Btu/h
- Return sensible heat credit
- 517,302.74Btu/h
- Source liquid enthalpy
- 343.62Btu/lb
- Receiver liquid enthalpy
- 180.13Btu/lb
- Receiver latent heat
- 970.14Btu/lb
- Annual fuel energy avoided
- 4,100.6MMBtu/yr
- Annual fuel savings
- 34,855USD/yr
- Annual water and treatment savings
- 11,191USD/yr
- Combined annual savings
- 46,046USD/yr
Calculation basis
- Isenthalpic flash
f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f - Heat credit
Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup) - Annual savings
Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]
Check the original case
Flash latent heat credit is zero. Both sensible heat and water savings come from returned liquid.
- Flash steam fraction16.85 %
- Flash steam used0 lb/hr
- Condensate returned3,592 lb/hr
- Combined annual savings46,046 USD/yr
Formulas and assumptions
Isenthalpic flash
f = (h_f1 − h_f2)/h_fg2; m_flash = m_in·f
The inlet is saturated liquid at P₁. Flow leaves the receiver as saturated vapor and saturated liquid at P₂.
Heat credit
Q_flash = m_flash,used·h_fg2; Q_return = m_return·(h_f2 − h_makeup)
The liquid credit percentage divides returned heat by all inlet sensible heat above cold make-up. Vapor credit uses latent heat, with no liquid return assumed from the vapor user.
Annual savings
Savings = hours·[(Q_flash + Q_return)·tariff/η + water volume rate·water tariff]
Water and treatment savings apply to returned liquid at an accounting density of 1,000 kg/m³. Enter the combined water and treatment tariff.
Worked examples
Open a case to edit its inputs.